解除固定固定关闭

中国区总部
毕孚自动化设备贸易(上海)有限公司

市北智汇园4号楼
静安区汶水路 299 弄 9-10 号
上海, 200072, 中国

+86 21 6631 2666
info@beckhoff.com.cn
www.beckhoff.com.cn/zh-cn/

KL1382 | Bus Terminal, 2-channel digital input, thermistor, 24 V DC, 30 ms

Image similar, may contain optional accessories
KL1382 | Bus Terminal, 2-channel digital input, thermistor, 24 V DC, 30 ms

KL1382 | Bus Terminal, 2-channel digital input, thermistor, 24 V DC, 30 ms

Signal LED 1
Error LED 1
Signal LED 2
Error LED 2
Power contact
+24 V
Power contact 0 V
+Input 1
-Input 1
+Input 2
+24 V
0 V
-Input 2
Top view 
Contact assembly 
KL1382 | Bus Terminal, 2-channel digital input, thermistor, 24 V DC, 30 ms

KL1382 | Bus Terminal, 2-channel digital input, thermistor, 24 V DC, 30 ms

The KL1382 digital input terminal analyzes the input signal from thermistor sensors with the aid of a current loop and a voltage of < 5 V. The bus terminal has two channels. The KL1382 is a monitoring device for thermal machine protection by PTC sensors and for the direct monitoring of motors, bearings and plants. In addition to the switching state, open circuit or short circuit is also detected. The LEDs display the signal states or any error states.

 

Special features:

  • suitable as a monitoring device for thermal machine protection, e.g. PTC sensors
  • direct monitoring of motors, bearings and plants with thermistor sensors
  • possibility to diagnose open circuit and short circuit

Product status:

regular delivery

Product information

Technical dataKL1382
Connection technology2-wire
Specificationthermistor PTC
Number of inputs2
Nominal voltage24 V (-15%/+20%)
“0” signal voltage≤ 1.5 kΩ
“1” signal voltage≥ 3 kΩ
Signal “0“ release≤ 1.5 kΩ
Signal “1“ excess temperature≥ 3 kΩ
Sensor voltage≤ 5 V
Diagnosticsopen-circuit monitoring > 8 kΩ, short-circuit diagnostic < 25 Ω
Input filter30 ms
Current consumption K-bustyp. 60 mA
Electrical isolation500 V (K-bus/field potential)
Bit width in the process image4 inputs
Configurationno address or configuration setting
Special featuresmonitoring device for thermal machine protection
Weightapprox. 55 g
Operating/storage temperature-25…+60°C/-40…+85°C
Relative humidity95%, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP20/variable
Pluggable wiringfor all KSxxxx Bus Terminals
Approvals/markingsCE, UL, ATEX, IECEx, DNV GL
Ex markingATEX:
II 3 G Ex ec IIC T4 Gc
IECEx:
Ex ec IIC T4 Gc
Housing dataKL-12-8pinKS-12-8pin
Design formcompact terminal housing with signal LEDsterminal housing with pluggable wiring level
Materialpolycarbonate
Dimensions (W x H x D)12 mm x 100 mm x 68 mm
Installationon 35 mm DIN rail, conforming to EN 60715 with lock
Side by side mounting by means ofdouble slot and key connection
Markinglabeling of the BZxxx series
Wiringsolid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver
Connection cross-sections*: 0.08…2.5 mm²,
st*: 0.08…2.5 mm²,
f*: 0.14…1.5 mm²
s*: 0.08…1.5 mm²,
st*: 0.08…1.5 mm²,
f*: 0.14…1.5 mm²
Connection cross-section AWGs*: AWG28…14,
st*: AWG28…14,
f*: AWG26…16
s*: AWG28…16,
st*: AWG28…16,
f*: AWG26…16
Stripping length8…9 mm9…10 mm
Current load power contactsImax: 10 A

*s: solid wire; st: stranded wire; f: with ferrule

Ordering information
KL1382Bus Terminal, 2-channel digital input, thermistor, 24 V DC, 30 ms
KS1382Bus Terminal, 2-channel digital input, thermistor, 24 V DC, 30 ms, pluggable wiring

Loading content ...

Loading content ...

© Beckhoff Automation 2024 - Terms of Use